Brought to you by:
Paper The following article is Open access

Experimental Research of Electromagnetic Interference Caused by Disconnector Operation in Gas Insulated Switchgear

, , , , and

Published under licence by IOP Publishing Ltd
, , Citation Tao Yang et al 2019 IOP Conf. Ser.: Mater. Sci. Eng. 486 012096 DOI 10.1088/1757-899X/486/1/012096

1757-899X/486/1/012096

Abstract

In order to intensively study the exterior transient electromagnetic interference characteristics caused by disconnector operation in Gas Insulated Switchgear, experimental research of exterior transient electromagnetic interference under switching conditions is performed in this paper. Based on 330kV GIS test platform, with the method of resistive impedance divider, TEV is measured with Pintech P6039A high-voltage probe and Yokogawa DLM2054 oscilloscope by using resistor voltage divider GIS exterior radiation electromagnetic circuit is also established using antenna theories, biconical antenna and spectrum analyzer etc. The exterior transient electromagnetic interference waveform and characteristics are precisely measured. By the contrast analysis of TEV and radiation electromagnetic waveforms, results can be summarized as followed: ① The TEV waveform caused by opening and closing of disconnecting switch is front sparse and rear dense, and its amplitude is low at the fore and high over the back; The electric field strength is weaker compared to the electromagnetic compatibility of normal substation.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.

Please wait… references are loading.
10.1088/1757-899X/486/1/012096